Purpose:To program delayed alarms, a condition must exist for a certain amount of time before the alarm is generated. A new alarm will not be created till the condition returns to normal and then returns to alarm at which time the delay timer starts again.
Format:DALARM expression , num , string
Description: expression is the alarm condition
num is the number of seconds to delay before causing an alarm
string is the alarm message with a length of up to 69 characters.
Example:10 DALARM FAN1 AND NOT FAN1_ST , 60 ,FAN1 NOT COMING ON
20 DALARM NOT FAN1 AND FAN1_ST , 60 ,FAN1 TURNED ON MANUALLY