14 How to use subnet

Description:
                  All subnets connected to MP can be used in the MP ,directly .
 
Format :
    1-48-VAR101
Description : This is a register  value of the Modbus ID 48  connected to pannel ID 1
Panel ID =1    (What's Panel ID ,please refer to Chapter 7  7.1.5)
Subnet Modbus ID =48
VAR101 : Register Number is 101
Notes : Register Number  is PLC  Address (Base 1). If you use Protocol Address (Base 0),
you must plus one to your current register number .
 
 
How to use in program:
EXAMPLE 1:GET THE VALUE OF THE REGISTER VALUE OF A SUBNET
 
10 REM *** THE VALUE OF 1-48-VAR101 ASSIGN TO VAR1 ***
20 VAR1 = 1-48-VAR101 
 
EXAMPLE 1:SET THE VALUE OF THE REGISTER VALUE OF A SUBNET
 
10  REM *** VAR1 ASSIGN TO  THE VALUE OF 1-48-VAR101  ***
20  1-48-VAR101 = VAR1
 
NOTE: When you use the register number ,you must know whether the register number can have the property of R/W.
 
Example show :
 
10 VAR1 = 1-48-VAR101
20 VAR2 = 1-48-VAR102
30 VAR3 = 1-47-VAR101
40 VAR4 = 1-47-VAR102
50 VAR5 = 1-20-VAR101
60 VAR6 = 1-20-VAR102
70 VAR7 = 1-19-VAR101
80 VAR8 = 1-19-VAR102
90 VAR9 = 1-44-VAR101
100 VAR10 = 1-44-VAR102
110 VAR11 = 1-46-VAR101
120 VAR12 = 1-46-VAR102
130 VAR13 = 1-49-VAR101
140 VAR14 = 1-49-VAR102
 
150 REM *** START COOLING PROCESS ***
160 IF VAR3 OR VAR5 OR VAR 7 OR VAR9 > 150 THEN START OUT1 , START OUT32
170 IF IN2 <= 160 THEN START OUT4, OUT5, OUT6, OUT7, OUT8, OUT9, OUT10, OUT11, OUT12, OUT13, OUT14
180 IF IN3 >= 700 THEN START OUT2
190 IF IN3 >= 850 THEN STOP OUT32 , STOP OUT2 , STOP OUT1
200 IF IN2 <= 20 THE STOP OUT32 , STOP OUT1
220 IF VAR3 = 100 THEN STOP OUT4 , STOP OUT11
230 IF VAR5 = 100 THEN STOP OUT5 , STOP OUT12
240 IF VAR7 = 100 THEN STOP OUT6 , STOP OUT13
250 IF VAR9 = 100 THEN STOP OUT7 , STOP OUT14
 
 
260 REM *** START COOLING PROCESS ROOM1 & ROOM6 ***
270 IF REM VAR1 OR VAR11 OR VAR13 > 240 THEN START OUT1 , START OUT32
280 IF IN2 < 200 THEN START OUT3, OUT8, OUT9, OUT10, OUT15, OUT16
290 IF IN3 >= 700 THEN START OUT2
300 IF IN3 >= 900 THEN STOP OUT32 , THEN STOP OUT2 , STOP OUT1 
310 IF IN2 <= 20 THE STOP OUT32 , STOP OUT1
320 IF VAR11 > 240 THEN START OUT3 , START OUT10
330 IF VAR11 = 200 THEN STOP OUT3 , STOP OUT10
320 IF VAR11 > 240 THEN START OUT8 , START OUT15
330 IF VAR11 = 200 THEN STOP OUT8 , STOP OUT15
340 IF VAR13 > 240 THEN START OUT9 , START OUT16
350 IF VAR13 = 200 THEN STOP OUT9 , STOP OUT16
 
 
360 REM *** START HUMIDIFIER PROCESS ***
380 IF VAR2 OR VAR4 OR VAR6 OR VAR 8 OR VAR10 OR VAR12 < 850 THEN START OUT2 ,START (OUT17 TO OUT23) , START (OUT10 TO OUT16) 
390 IF IN3 < 450 THEN START OUT1 , START OUT32
400 WHEN IN3 = 700 THEN STOP OUT1 , STOP OUT32
410 IF VAR2 OR VAR4 OR VAR6 OR VAR 8 OR VAR10 OR VAR12 > 950 THEN STOP OUT32 , OUT2